PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
2
8
N terminal
L1 wire connected to
L1 terminal
L2 wire connected to
L2 terminal
Equipment ground wire
connected to ground bar
Figure 4.2.1 – AC Terminal Block for AC Wiring Connections
Connect the AC equipment GND wire to the screw of the ground bar labeled
Connect the white N wire to the terminal labeled N of the AC terminal block.
Connect the L1 wire to the terminal labeled Line1 of the AC terminal block.
Connect the L2 wire to the terminal labeled Line2 of the AC terminal block.
Tighten the screws with a torque of 15.6 in-lb (1.7Nm)
Reconfirm that all connections are correct as described above and all screws are properly
tightened.
WARNING: Each connection to a PVI 3000S-5300 inverter must be installed with a
dedicated circuit breaker. No other appliances may be connected to the circuit
breaker.
4.3 DC Wiring
WARNING: Remove all PV string fuses before wiring DC connections! Do not
reinstall fuses until you are ready to commission the inverter (See commissioning
Section 5.0).
WARNING: Do not use fuses larger than 15A for the PV string fuses!