PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
2
8
N terminal
L1 wire connected to
L1 terminal
L2 wire connected to
L2 terminal
Equipment ground wire
connected to ground bar
Figure 4.2.1 – AC Terminal Block for AC Wiring Connections
•
Connect the AC equipment GND wire to the screw of the ground bar labeled
• Connect the white N wire to the terminal labeled N of the AC terminal block.
• Connect the L1 wire to the terminal labeled Line1 of the AC terminal block.
• Connect the L2 wire to the terminal labeled Line2 of the AC terminal block.
• Tighten the screws with a torque of 15.6 in-lb (1.7Nm)
• Reconfirm that all connections are correct as described above and all screws are properly
tightened.
WARNING: Each connection to a PVI 3000S-5300 inverter must be installed with a
dedicated circuit breaker. No other appliances may be connected to the circuit
breaker.
4.3 DC Wiring
WARNING: Remove all PV string fuses before wiring DC connections! Do not
reinstall fuses until you are ready to commission the inverter (See commissioning
Section 5.0).
WARNING: Do not use fuses larger than 15A for the PV string fuses!