Installation
5.7.4 Assembly steps of AC connector
SolarRiver series inverters are designed for single phase grid. Technical data should comply with the
rule of local public grid.
Table 3 Cable and Micro-breaker rule
Micro-breaker should be installed between inverter and grid, and the residual current is 30 mA≤Ifn≤300 mA.
Any load should not be connected with inverter directly.
Figure 13 Incorrect Connections between Load and Inverter
18
Input
Output
ESC OK
Impedance of SolarRiver-D inverter AC connector should be less than 2Ω. To ensure anti-islanding
function reliable, wire loss power of PV cable should <1% of normal power. Length between inverter
AC side and grid connecting dot should be less than 150m. Relationship between cable and cable loss
is as following:
Figure 14 AC Cable Loss
Cable (Cu)
Micro-Breaker
25A20A 20A 32A32A
Model
SolarRiver
3400TL-D
SolarRiver
4000TL-D
SolarRiver
4500TL-D
SolarRiver
5000TL-D
SolarRiver
5200TL-D
4mm² 4mm² 4mm² 6mm²6mm²