6.4 Ground Fault Interrupt Device
The inverter is equipped with a Ground Fault Detector Interrupter (GFDI). The purpose
of the GFDI is to detect a ground fault (unintended current ow from the solar panels to
earth ground) and in this event, disable the inverter.
!
WARNING
For the GFDI circuit to function as designed, the solar array safety ground
must not be connected to the PV array positive or negative leads.
Bonding the safety ground to the grounded leg of the array anywhere but
through the inverter will cause the GFDI circuit to be bypassed. This would
defeat the operation of the GFDI and potentially create an unsafe operating
condition.
!
AVERTISSEMENT
Pour que le circuit GFDI fonctionne normalement, la prise de terre de sécurité
du système PV ne doit pas être branché aux câbles positifs ou négatifs des
piles PV.
Brancher la prise de terre de sécurité au pied des piles ou à toute autre partie
que l’onduleur causerait une mise hors circuit du GFDI. Ceci ne empêcherait
le fonctionnement normale du circuit GFDI et créerait des conditions de
fonctionnement potentiellement dangereuses.
The GFDI functions using a 5A fuse to connect or bond the solar array Negative (or the
solar array Positive, if using a positively grounded panel array) to earth ground on the DC
Distribution PCB.
If the ground fault current exceeds 5A between the grounded array terminal and the earth
ground, the fuse will open and disconnect the solar panels from their ground reference,
interrupting the ground fault. In this situation, the inverter will cease operation and
display a fault message (see
Appendix D - Limits, Fault Codes, Torque Values, and Wire
Sizes
).
Figure 6-9 Ground Fault Error Message
If the inverter displays a ground fault as shown in Figure 6-9, turn OFF the AC and DC to
the inverter and refer to
Chapter 7, Maintenance & Troubleshooting
.